How Redundancy Works

Ignition redundancy supports 2-node systems. One node is considered the master node, and the other is the backup node. Both nodes share the same "state", or configuration. In other words, all projects, gateway settings, etc. are shared between the nodes. The management of the configuration is performed by the master node, and then replicated to the backup node.

Node Communication

The master and backup nodes communicate over TCP/IP. Therefore, they must be able to see each other over the network, through any firewalls that might be in place. All communication goes from the backup to the master node, by default on port 8750. Therefore, that port must allow TCP listening on the master machine. The port can be changed in the gateway redundancy settings page.

Configuration Synchronization

The master node maintains the official version of the system configuration. All changes to the system must be made on the master- the gateway on the backup will not allow you to edit properties. Similarly, the designer will only connect to the master node.

 

When changes are made on the master, they are queued up to be sent to the backup node. When the backup connects, it retrieves these updates, or downloads a full system backup if it is too far out of date.

 

If the master node has modules that aren't present on the backup, they will be sent across. Both types of backup transfers- "data only" and "full"- will trigger the gateway to perform a soft reboot.

Runtime State Synchronization

Information that is only relevant to the running state, such as current alert states, is shared between nodes on a differential basis, so that the backup will take over with the same state that the master had. On first connection, or if the backup node falls too far out of sync, a full state transfer is performed. This information is light-weight and will not trigger a gateway restart.

Status Monitoring

Once connected, the nodes will begin monitoring each other for liveliness and configuration changes. While the master is up, the backup runs according to the standby activity level in the settings. When the master cannot be contacted by the backup for the specified amount of time, it is determined to be down, and the backup assumes responsibility. When the master becomes available again, responsibility will be dictated by the recovery mode, and the master will either take over immediately, or wait for user interaction.

System Activity

When a node is active, it runs fully, connecting to any configured OPC servers, and communicating with devices. When it is not active, its activity level is dictated by the settings, either warm or cold. In "warm" standby, the system will run as if it were active, with the exception of logging data or writing to devices, allowing for faster fail-over. In "cold" standby, the system does not subscribe to tag values, and does not communicate with any device. This allows the system to standby without putting additional load on the devices and network. Fail-over will take slightly longer, as tags must be subscribed and initialized.

Historical Logging

Historical data presents a unique challenge when working with redundancy, due to the fact that it is never possible for the backup node to know whether the master is truly down, or simply unreachable. If the master was running but unreachable due to a network failure, the backup node would become active, and would begin to log history at the same time as the master, who is still active. In some cases this is OK because the immediate availability of the data is more important than the fact that duplicate entries are logged, but in other cases, it's desirable to avoid duplicates, even at the cost of not having the data available until information about the master state is available. Ignition redundancy provides for both of these cases, with the backup history level, which can be either "Partial" or "Full". In "full" mode, the backup node logs data directly to the database. In "partial" mode, however, all historical data is cached until a connection is reestablished with the master. At that time, the backup and master communicate about the uptime of the master, and only the data that was collected while the master was truly down is forwarded to the database.

Client Fail-over

All Vision clients connect to the active node. When this system fails and is no longer available, they will automatically retarget to the other node. The reconnection and session establishment procedures are handled automatically, but the user will be notified that they have been transferred to a different node, so that they can notify the system administrator that the system may need attention.